标题:Research on Fast Fault Isolation and Restoration for Distribution
作者:Ma, Shicong; Xu, Bingyin; Deng, Feng; Bo, Zhiqian
通讯作者:Ma, S
作者机构:[Ma, Shicong; Bo, Zhiqian] ALSTOM GRID UK, London, England.; [Xu, Bingyin] Shandong Univ Technol, Zibo, Peoples R China.; [Deng, Feng] Changsha Un 更多
会议名称:Asia-Pacific Power and Energy Engineering Conference (APPEEC)
会议日期:MAR 25-28, 2011
来源:2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC)
出版年:2011
DOI:10.1109/APPEEC.2011.5748508
关键词:Distribution automation; Fault Isolation and restoration;; Non-effectively earthed network; Transient zero mode current; Optical; fiber Ethernet
摘要:A new fault isolation and restoration technique for distribution automation, which employs local Ethernet network, is presented. It can isolate all short circuit faults in the loop within 300ms and restore the supply of healthy sections in less than 1.2 seconds. A reliable fault location method for isolating the single phase to ground fault in the non-effectively earthed network, which makes use of the fault generated transient signals is also proposed. The simulation and Laboratory test results show the proposed techniques are reliable and feasible.
收录类别:CPCI-S;EI;SCOPUS
资源类型:会议论文;期刊论文
原文链接:https://www.scopus.com/inward/record.uri?eid=2-s2.0-79955792340&doi=10.1109%2fAPPEEC.2011.5748508&partnerID=40&md5=2cb45bb6b8a2db3ee87dca306e05c1ff