标题:Study on the hotspot distribution characteristics of oil immersed transformer based on electromagnetic-fluid-thermal fields coupling analysis
作者:Cui, Jingxian ;Zhao, Tong ;Zhang, Yuantao ;Guo, Yongkang ;Zou, Liang
作者机构:[Cui, Jingxian ;Zhao, Tong ;Zhang, Yuantao ;Guo, Yongkang ;Zou, Liang ] School of Electrical Engineering, Shandong University, Jinan, Shandong; 250061 更多
会议名称:2017 China International Electrical and Energy Conference, CIEEC 2017
会议日期:October 25, 2017 - October 27, 2017
来源:CIEEC 2017 - Proceedings of 2017 China International Electrical and Energy Conference
出版年:2017
页码:451-455
DOI:10.1109/CIEEC.2017.8388490
摘要:Power transformer is one of the key equipment in power system. The main failure factor of oil immersed transformers is the high temperature generated during operation. Therefore, it is necessary to study the hotspot distribution of iron core and winding temperature of oil immersed transformers. This paper analyzes the tendency of winding, iron core and oil in the course of temperature rise and cooling stage. And the distribution area of hotspot temperature is clear eventually. Three-dimension model of oil immersed transformer is established by the finite element software. And the distribution of temperature can be obtained through the accurate calculation and analysis on the coupling field of electromagnetic-fluid-thermal. The conclusion of electromagnetic analysis is generated into the thermal field model as the pre-additive load in the thermal analysis. The conclusion of thermal characters studied before is verified. And a deeper comprehension of hotspot temperature is obtained simultaneously.
© 2017 IEEE.
收录类别:EI
资源类型:会议论文