标题:Simulation of VFTO Suppression Methods for 1100kV GIS Substation
作者:Gong, Wenxiu; Wang, Peijin; Li, Qingquan; Xue, Weijian; Qiao, Mu; Wang, Xiao; Pang, Yumei
通讯作者:Gong, WX
作者机构:[Gong, Wenxiu; Wang, Peijin; Li, Qingquan] Shandong Univ, Sch Elect Engn, Jinan, Shandong, Peoples R China.; [Xue, Weijian; Qiao, Mu; Wang, Xiao; Pa 更多
会议名称:IEEE 3rd Information Technology, Networking, Electronic and Automation Control Conference (ITNEC)
会议日期:MAR 15-17, 2019
来源:PROCEEDINGS OF 2019 IEEE 3RD INFORMATION TECHNOLOGY, NETWORKING, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (ITNEC 2019)
出版年:2019
页码:987-991
DOI:10.1109/ITNEC.2019.8729057
关键词:GIS; VFTO; suppression methods
摘要:Disconnector switch operation in GIS will generate VFTO, which will harm the equipment. Because there are many limitations in field measurement, simulation can overcome the limitations of experimental research, which can replace test measurement to a certain extent. In this paper, three VFTO suppression methods are simulated in ATP-EMTP. By comparing the VETO amplitudes of the main equipment before and after the suppression measures, the results show that the paralleling closing resistor can significantly reduce the VFTO amplitude of major equipment. Simplifying wiring also have better suppression but will increase the VFTO amplitude of some devices.Although installing the wave blocker can reduce the VFTO steepness and amplitude on the transformer, but it will produce a serious VFTO on the wave blocker. So the latter two methods can only be applied when appropriate. Through this research, to find the application of the suppression measures, thus effectively reducing the hazard of the VFTO in GIS.
收录类别:CPCI-S;EI;SCOPUS