标题:Analysis of Insulation Aging Performance of Medium Voltage Crosslinked Polyethylene Cable During Operation
作者:Song, Pengxian; Fang, Shengchen; Liu, Jiping; Zhang, Yuqi; Wang, Haoming; Meng, Fansong
通讯作者:Song, PX
作者机构:[Song, Pengxian; Fang, Shengchen; Liu, Jiping; Wang, Haoming] State Grid Tianjin Elect Power Res Inst, Tianjin 300000, Peoples R China.; [Zhang, Yuq 更多
会议名称:China International Conference on Electricity Distribution (CICED)
会议日期:SEP 17-19, 2018
来源:2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED)
出版年:2018
页码:530-533
DOI:10.1109/CICED.2018.8592202
关键词:cross-linked polyethylene; aging; power cable; dielectric loss
摘要:In order to explore the characteristics of insulation aging changes of medium voltage cross-linked polyethylene cables after running for a period of time, the dielectric loss of 35 kV cable insulation with new cable and actual operating life of la, 3a, 5a, 7a, 10a was studied. Axial slicing was performed on the inside and outside of the cable with different operating years. A flat sample with a surface of 1 mm thickness was prepared and tested. The experimental results show that the low frequency dielectric loss factor of XLPE correlates with the aging degree. When the frequency is below 0.1 Hz, the tangent of dielectric loss angle shows a linear upward trend with the aging degree. The outer dielectric loss of the actual running cable insulation is greater than the inner side, indicating that environmental factors may be the main cause of insulation aging of the running cable. The detection of dielectric loss can evaluate the external environment of the running cable, the main insulation aging cause, and the aging degree. It is a simple and effective method suitable for practical engineering applications.
收录类别:CPCI-S;EI;SCOPUS
资源类型:会议论文;期刊论文