标题:Ultra-Low Frequency Dielectric Loss Detection and Aging State Evaluation of 10kV XLPE Cable
作者:Song, Pengxian; Liu, Jiping; Wang, Haoming; Meng, Fansong; Fang, Shengchen; Zhang, Yuqi
通讯作者:Song, PX
作者机构:[Song, Pengxian; Liu, Jiping; Wang, Haoming; Fang, Shengchen] State Grid Tianjin Elect Power Res Inst, Tianjin 300000, Peoples R China.; [Meng, Fans 更多
会议名称:China International Conference on Electricity Distribution (CICED)
会议日期:SEP 17-19, 2018
来源:2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED)
出版年:2018
页码:534-537
DOI:10.1109/CICED.2018.8592499
关键词:ultra-low frequency; dielectric loss; water tree deterioration; cross; linked polyethylene
摘要:In this paper, the effectiveness of ultra-low frequency dielectric loss in evaluating the insulation aging state of XLPE cables is described. The ultra-low frequency dielectric loss of 21 10kV cables in Tianjin area was measured. On the basis of the analysis of the relationship between the ultra-low frequency dielectric loss and the aging of insulated water branch aging, according the International Society of Electrical Engineers IEEE400.2-2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency(VLF)(less than 1Hz), the test date are analyzed. The results are shown that 9 of the 21 cables are in a state of need for further test or maintenance. The longer the service time, the more cable failures, the more serious the aging degree. The ultra-low frequency dielectric loss can effectively evaluate the insulation aging state of XLPE cables, which is of great significance for guiding the reconstruction of the distribution network cable in Tianjin.
收录类别:CPCI-S;EI;SCOPUS
资源类型:会议论文;期刊论文
原文链接:https://www.scopus.com/inward/record.uri?eid=2-s2.0-85063139852&doi=10.1109%2fCICED.2018.8592499&partnerID=40&md5=29555bc178c64f9465e82526eeeb57ff