标题:Complete Protection Scheme for Active Closed-loop Distribution Systems
作者:Pan, Zhiyuan; Li, Hongwei; Wang, Jing; Si, Xinyue
通讯作者:Pan, ZY
作者机构:[Pan, Zhiyuan; Li, Hongwei; Wang, Jing] State Grid China Technol Coll, Jinan, Peoples R China.; [Si, Xinyue] Shandong Univ, Sch Elect Engn, Jinan, P 更多
会议名称:5th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies (DRPT)
会议日期:NOV 26-29, 2015
来源:2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015)
出版年:2015
页码:1157-1161
关键词:Closed-loop; Distribution system; Protection; Distributed generation;; Current phase variation
摘要:With increasing integration of distributed generation (DG) to the active distribution systems, the existing grid structure and protection configuration cannot meet the requirements of reliability. Adopting closed-loop configuration and reasonable protection schemes, it is possible to reduce the range of power outage and ensure continuous supply of DG. Firstly, an IED (intelligent electronic device) based complete protection structure consisting of several protection functions is proposed, including line protection, load protection and node protection. The protection principles of each protection function is described. The paper also studies the single-terminal w eak-infeed issue of closed-loop distribution system by theoretical and simulation analysis. It is proved that the current phase variation based line protection function is not affected by the magnitude of fault current. It could correctly identify the fault under single-terminal weak-infeed condition.
收录类别:CPCI-S
资源类型:会议论文